JetPanel

Serverracks in data centers can vary in load and heat. Especially server virtualization and cloud technologies can lead to changing workloads.

As a result an under- or oversupply of cold air can occur.

This can either cause unnecessary operation expenses or hot spots which might lead to server failure.

With JETpanel hot spots can be eliminated exactly at their occurrence without additional ducting housings or any other installations.

The air supply is regulated via a control unit according to preset set points.

They reduce the global fan performance of the CRAC unit and supply air where needed.

JetPanel

3D View

We have prepared a interactive 3D model. You can take a closer look at a Hydrologic Panel here.

The JETpanel of Weiss Doppelbodensysteme GmbH can easily be integrated in a new or existing raised floor pattern.

A powerful EC-fan is available in two different performance levels. Target and eliminate your data center troubles.

JETpanel is made from a DIN EN 12825 certified steel ventilation panel with 39% free surface area and an EC-fan.

A central control unit can cover up to 4 temperature units.

The assigned JETpanels operate, according to the set points.

  • Airsupply on demand
  • Easy installation, plug and play
  • EC-fan for spot air supply
  • Airvolume up to 2.700 m³ or 4.000 m³/h
  • Low powerconsumption
  • No enclosures of cold aisles necessary

Technical Data

Panel

Admeasurement
600 x 600 mm
Thickness
 250mm, without panel
Topside
PVC, HPL, rubber
Bottomside
EC-Ventilatoren
Weight
26 kg
Material
Steel, powder coated
Building Material class
A1
Freier Free Surface
39%
Resistance to ground
< 10⁸ Ohm (Depends on covering)

Performance

Voltage
230 V
Power consumption
140 W
400 W XL Version
Air flow
2700 m³/h
4000 m3, versión XL

Load bearing capacity

Pointload
3kN
Ultimateload
<6kN
Finish floor heights
350 – 2000 mm